Technical information
C:
\
UFFICIO TECNICO
\
MANUALI
\
ML2
00
\
ML200 INGLESE
\
34
If for sev
eral reasons you need to change the level of block of the instrument, follow the steps:
?? Set the dip switch on OFF position (opposite side than the lock symbol, see pict. On page 32)
?? Access the Main Menu (see page 32)
?? Press several times the key , till you don’t reach the menu “11: Internal data” and then press
?? Press the key and to enter the function “Block level”
?? Choose the desired level of block by pressing the key and confirm the choice by pressing the key
To enable the level of bl
ock you selected place back the DIP switch to the original ON position marked with a lock symbol
(see pict. On page 32)
The available levels of block are the following:
Level 0: it completely disables the access to the functions. You can perform the following functions through the keyboard:
?? Changing the display mode
?? Dosing Start/stop (when such a function is enabled)
?? Data printing (when such a function is enabled)
Level 1: it enables the access to the following functions:
?? Totalisers re-setting
?? Dosing functions modifications
Level 2: it enables the access to the following functions:
?? Quick start menu (see code level 2 = 11111)
?? Scale (full enabling)
?? Display (partial enabling)
?? Diagnostics (partial enabling)
Livello 3: it enables the access to all the functions of level 2
When the Dip-switches are on OFF position, all the functions are enabled.
The functions requiring an access code higher than L2 are reserved to the service.
BLOCK LEVELS