Technical information

C:
\
UFFICIO TECNICO
\
MANUALI
\
ML2
00
\
ML200 INGLESE
\
27
(Out1)
(Out2)
(Out1)
(Out2)
On/off outputs wiring(Up to 1250 HZ) (low frequency):
OUT 1/OUT 2 standard
OUT 3/OUT 4 with modules (page 24)
On/off output wiring (Up to 12500 HZ) (high frequency): only with ME 201 module
Terminal 16 18
Terminal 17 19
43 V
+
43 V
Terminal 30
Terminal 29
On/off outputs wiring(Up to 1250 HZ)
On/off output wiring (Up to 12500 HZ)
- Opto-insulated output with floating collector and emitter terminals
freely connectable
- Maximum switching voltage: 40 Vdc
- Maximum switching current: 100mA
- Maximum saturation voltage between collector and emitter @100mA:
1,2V
- Maximum switching frequency (load on the collector or emitter,
RL=470? , VOUT=24Vdc): 1250Hz
- Maximum revers current bearable on the input during and accidental
polarity reversion (VEC): 100mA
- Insulation from other secondary circuits: 500 Vdc
- Opto-insualted output with floating collector and emitter terminals
freely connectable. In order to get the maximum performances it is
necessary to connect the emitter to the common terminal of the
outputs (0V), while the load has to be on the collector. This output is
internally connected to the power supply source 24 Vdc available on
the terminal block.
- Maximum switdhing voltage: 40Vdc
- Maximum switdhing current: 100mA
- Maximum saturation voltage between collector and emitter @ 100mA,
load on the collector and internal power supply: 0,3V
- Maximum saturation voltage between collector and emitter @ 100mA,
load on the emitter and internal power supply: 3V
- Maximum switching frequency, load on the collector and internal
power supply: (RL=470? , VOUT=24Vdc): 12500Hz
- Maximum switching frequency, load on the emitter or external power
supply: (RL=470? , VOUT=24Vdc): 2500Hz
- Insulation from the other secondary circuits (except 24V and 4…20mA
outputs): 500 Vdc