3.3 Connection of the Proven Draft Switch and Stack Probe
The Proven Draft Switch (PDS) must be installed indoors, in the vertical position (pre-drilled knockouts face down).
Mountthecontroluprighttoawallorotheratsurface.DoNOTlaythecontroldownormounthorizontally.
A Proven Draft Switch (PDS) must be used with the ADC100 control as a system safety device. The PDS monitors the
pressureinsidethestackandsignalsthecontroltoshutdowntheapplianceifinsufcientdraftexists.Astackprobe
senses the pressure read by the PDS and is connected via silicone tubing.
The silicone tubing supplied with the PDS should be connected to the NEGATIVE (-) port of the PDS. This is the bottom
port on the switch. The standard tube length is 6 feet. The distance can be extended up to 25 feet by using 1/4” rigid
plastic or copper tubing as temperature allows (not supplied).
3.4 Installation of the Chimney Probe
The probe must be installed between the appliance and the exhaust fan. If a damper is used in the system, the probe
should be installed between the appliance and damper.
Locatetheprobeatleastadistancethree(3)ventdiametersawayfromanyelbow,teeordamper.Forreplace
installations, the probe should be installed close to the fan inlet. See Fig. 5.
To produce an accurate pressure reading, theprobeshouldbeinstalledushwiththeinnerwallofthechimneyor
stack.Ifdoublewalledstackisused,theprobeshouldbeushwiththeinnermostwall.
+
-