Specifications
13
3916067 01.13
5.StartupandConguration
5.1 General
Dip switches are located on the control board to allow the user to specify certain functions of the ADC100. Verify
settings using the table below.
NOTE: Do NOT turn PDS check off unless requested by the factory technical support.
DIP SWITCH NAME OFF ON
DEFAULT
POSITION
1
(Left)
MANUAL
RESET
Automatic reset
at power failure or
insufcientdraft
Manual reset at
power failure or
insufcientdraft
OFF
2
(Center)
MANUAL
ADJ
Automatic Mode-control
speeds up fan if PDS
opens during operation
Manually adjust
fan speed using
potentiometer
OFF
3
(Right)
PDS
CHECK*
No monitoring to see
if the PDS was in NC
position prior to start
The PDS must be
in NC position prior
to start
ON