5.StartupandConguration
5.1 General
Dip switches are located on the control board to allow the user to specify certain functions of the ADC100. Verify
settings using the table below.
NOTE: Do NOT turn PDS check off unless requested by the factory technical support.
DIP SWITCH NAME OFF ON
DEFAULT
POSITION
1
(Left)
MANUAL
RESET
Automatic reset
at power failure or
insufcientdraft
Manual reset at
power failure or
insufcientdraft
OFF
2
(Center)
MANUAL
ADJ
Automatic Mode-control
speeds up fan if PDS
opens during operation
Manually adjust
fan speed using
potentiometer
OFF
3
(Right)
PDS
CHECK*
No monitoring to see
if the PDS was in NC
position prior to start
The PDS must be
in NC position prior
to start
ON