Specifications
11
3916067 01.13
4.4WiringofaGasFireplacewithaDamper
TointerlocktheADC100withagasreplaceasshowninFig.9,connecttheAuxiliaryInterminals9and10onthe
control board to a wall switch. Either by using line voltage or use board voltage from terminals 7 and 8 as depicted
ingure8.ConnectthegasvalveorignitiontoAuxiliaryOutatterminals22and23.TheAuxiliaryOutisanormally
opendrycontactthatcloseswhenthePDSclosesandreleasesthereplaceforoperation.TheAuxiliaryInterminals
are rated for maximum 250/125 VAC/VDC.
NOTE: Ifanelectronicignitioncontrolisusedwiththereplace,doNOTinterlockitwithdamperactuator.
Damper actuator should interlock with the ADC100 control only.
To interlock the damper to the control, connect the actuator to terminals 14 and 15 as shown in Fig. 9. The actuator
must include an endswitch to enable the damper prove function. The damper prove function is a dry contact that
closes when the damper proves open. Connect the Common and Normally Open terminals of the actuator endswitch to
terminals 16 and 17 on the board.
Note: See Fig. 10 in Section 4.5 for connection of 3-phase fan with VFD.
ADC 100
XTP
26 27 28
Fig.9