9-16 InterReach Unison Installation, Operation, and Reference Manual PN 8700-10
620003-0 Rev. B
9.3.2.1 Troubleshooting Main Hub LEDs During Normal Operation
All of the Main Hub’s LEDs should be green during normal operation. If any LEDs
are red, get status using AdminManager to determine the exact cause and recom-
mendations.
Table 9-10 Troubleshooting Main Hub Port LEDs During Normal Operation
During
Normal
Operation
Main Hub
Port LEDs State Action Impact
Expansion
Hub Not
Connected
LINK
Red If the Expansion Hub was discon-
nected accidentally, re-connect the
cables. The LEDs should change to
Green/Red (then Green/Green, after
20 seconds, if the Main Hub band
has been programmed).
If the Expansion Hub is to be
removed from service permanently,
then use AdminManager’s ‘Clear All
Disconnect Status’ command to
clear all disconnect states to no con-
nect states. The Main Hub’s port
LEDs should change to Off/Off.
Expansion Hub was previously con-
nected, but it is not currently con-
nected; Expansion Hub cable
disconnect.
AdminManager will clear all discon-
nects caused by installation as part of
the clean-up process. After installation,
power cycle the Main Hub or use
AdminManagers “Clear All Discon-
nect Status” command.
E-HUB/RAU
Off
Expansion
Hub
Connected
LINK
Red Use AdminManager to determine the
exact cause of the Main Hub’s faults.
Lost communication with Expansion
Hub; could be Expansion Hub problem
or fiber cable problem.
E-HUB/RAU
Off
LINK
Green Expansion Hub or connected RAU
reports a fault condition; use Admin-
Manager to determine the exact
cause of the Expansion Hub and
RAU’s faults.
Degraded performance or unit may be
off-line.
Depends on fault condition.
E-HUB/RAU
Red