User's Manual
7-2 InterReach Unison Installation, Operation, and Reference Manual PN 8700-10
620003-0 Rev. B
7.1.3 Multiple Operator System Recommendations
As in any Unison system, a multiple operator (neutral host) system requires one pair
of fiber strands between each Main Hub and each Expansion Hub, and one Cat-5/6
cable between each Expansion Hub and each RAU. In situations where Hubs and/or
RAUs will be installed in the future to support the addition of frequency bands and/or
wireless Operators, it is advantageous to install the necessary cabling initially. Such
deployment typically leads to substantial cost savings over installing parallel cabling
at separate times.
7.1.4 Distance Requirements
The following table shows the distances between Unison components and related
equipment.
Table 7-1 Unison Distance Requirements
Equipment
Combination Cable Type Distance Additional Information
Repeater to Main
Hub
Coaxial; N male
connectors
3–6 m (10–20 ft) typical Limited by loss and noise.
Refer to your link budget
calculation.
10 m (33 ft) maximum Limited by CE Mark require-
ments.
Base Station to Main
Hub
Coaxial; N male
connectors
3–6 m (10–20 ft) typical Limited by loss and noise.
Refer to your link budget
calculation.
10 m (33 ft) maximum Limited by CE Mark require-
ments.
Main Hub to
Expansion Hub
Multi-mode Fiber:
Single-mode Fiber:
SC/APC male
connectors
1.5 km (4,921 ft) max.
6 km (19,685 ft) max.
Limited by 3 dB optical loss.
Expansion Hub to
RAU
Cat-5/6 ScTP;
shielded RJ-45 male
connectors
• Minimum: 10 meters (33 ft)
• Recommended Max.: 100 meters (328 ft)
• Absolute Max.: 150 meters (492 ft)
See “System Gain (Loss)
Relative to ScTP Cable
Length” on page 6-27.
RAU to passive
antenna
Coaxial; SMA male
connectors
1–3.5 m (3–12 ft) typical Limited by loss and noise.
Refer to your link budget
calculation.