User's Manual

Table Of Contents
Help Hot Line (U.S. only): 1-800-530-9960 7-43
D-620003-0-20 Rev M CONFIDENTIAL
Connecting Contact Alarms to a Unison System
NOTE: LGCell and FlexWave Focus support only faults (major alarms).
Do not mix LGCell and Unison Main Hubs in the same daisy-chain. You can
daisy-chain multiple LGCell Main Hubs together and use the Alarm Sense Adapter
Cable to connect the chain to a Unison Main Hub, which will act as an alarm sensor.
7.7.1 Alarm Source
Unison always acts an alarm source, no matter what type of equipment you are con-
necting to. Refer to Section 7.7.2 on page 7-46 if you want Unison to sense LGCell
contact closures or other external alarms.
Using FlexWave Focus to Monitor Unison
When you connect FlexWave Focus to Unison, the Unison Main Hub is the output of
the alarms (alarm source) and Focus is the input (alarm sense), as shown in the fol-
lowing figure. Focus supports only faults (major alarms).
Figure 7-12 Connecting FlexWave to Unison
Unison Main Hub
RF OUT
DOWNLINK
RF IN
UPLINK
FIBER
UPLINK
DOWNLINK
ALARM
RS-232C
FlexWave
Focus
RFM
Alarm
Sense
Alarm
Source
Alarm
Source
5-port Alarm Daisy-Chain Cable
9-pin Adapter