User's Manual
ADCP-75-348 • Issue 1 • 04/2008
Page 16
© 2008, ADC Telecommunications, Inc.
6.7 Coaxial Cable Connections
The RF interface between the HU DART card and the EBTS/BTS is supported through two type
QMA female connectors mounted on each DART front panel. One connector provides the
coaxial cable connection for the forward path (downlink) signal and the other connector
provides the coaxial cable connection for the reverse path (uplink) signal.
In most installations, it is usually necessary to insert an
external attenuator
into the forward path
link between the HU and the BTS. A signal level that is greater than –9 dBm will overdrive and
possibly damage the HU receiver. Before completing the forward path connection at the BTS,
verify that the composite forward path RF signal level at the HU is between
–25 and +5 dBm
.
The HU should be mounted as close as possible to the EBTS/BTS to minimize cable losses. Use
the following procedure to route and connect the forward and reverse path coaxial cables to the
HU DART cards:
1. Obtain the required lengths of high performance, flexible, low loss 50-ohm coaxial
communications cable (RG-400 or equivalent) for all coaxial connections.
2. Route the forward and reverse path coaxial cables between the HU and the BTS interface
(per system design plan) and cut to the required length. Allow sufficient slack for dressing
and organizing cables at the HU and for installing an external attenuator in the forward
path link.
3. Terminate each cable with an QMA-Type male connector following the connector
supplier’s recommendations.
4. If required, install an external attenuator in the forward path.
5. Connect the forward path cable to the FWD RF IN connector on the HU DART front
panel as shown in
Figure 12.
6. Connect the reverse path cable to the REV RF OUT connector on the HU DART front
panel (see
Figure 12).
7. Repeat this procedure for the remaining DART cards in the HU.
8. Dress and secure cables at the right side of the HU.
9. Complete all remaining coaxial connections as specified in the system design plan.
Note: The composite forward path RF signal level at the HU must be between –25 and
+5 dBm. Do not connect the forward path cable until the composite forward path RF
signal level is measured and the amount of external attenuation required is determined.