Install the RF Module(s)
Page 36 FlexWave Prism RF Modules for Prism Remote Units Installation Guide
© 2012 TE Connectivity Ltd TECP-77-141 • Issue 1 • April 2012
ConnecttheRFModuleCables
11 PositionthecablessothattheyareundertherightedgeoftheRFModule,pointingup.
12 FollowtheruleslistedbelowwhenconnectingtheRFModulecables.
AlwaysprovidedateachRFModuleshelfarefivecables:
onePower(PWR)cable
twoRFcables(TX0/RX0)and(TX1/RX1)
twohigh‐speed‐datacables,whichinthisdocumentarereferredtoasLow‐Voltage
DifferentialSignaling(LVDS)cables.
LVDScableslabeledPRIMandDIVshouldalwayseitherbeconnectedorstrainrelievedto
adjacentcables.Thisprotectsagainstthecablegettingcaughtinthechassisdoor.
MakesurethetwoLVDScablesarefullyseatedandlockedintotheirconnectors.
IfyouareinstallingamoduleintoaDiversityChassis,bothRFcableslabeledMODN
TX0/RX0
andMODNTX1/RX1willbepopulated.
ForDiversitymodules,allcablesaretobeconnected.
WhenyouorderaDualSuperDARTmodule,connectbothLVDScables(PRIMandDIV)and
the
RFTX0/RX0cable.
Adheretoaminimumbendradiusof1‐inchforallRFcablesfromtheintegratedcable
guidetothemodule.
Maintainadequatestrainreliefdistancesfromconnectionpointstothemodule.
WheninstallingDual‐SlotRFmodules:
TheupperRFModuleshelfwilleithernotbepresent(factoryinstalledmodule)orwill
beremovedpriortoinstallation(fieldinstalledmodule).
ForDual‐Slotmodules,onlytheRFcablelabeledMODNTX0/RX0onthelowermodule
slotwillbeconnectedtothemoduleconnector
TX0/RX0.
TheMODNTX1/RX1cableshouldbesecuredtothecablebundleusingtheprovided
cabletie.
EnsurethattheMODNTX1/RX1cableandconnectoraresecuredsothattheywillnot
bepinchedorpreventthePRUdoorfromclosing.
ThePower(PWR)cableandtwoLVDScablesoftheupperRFModuleslotwillnotbe
used.ConnecttheRFcablelabeled
MODNTX1/RX1totheconnectorlabeledN/Conthe
upperhalfofthedouble‐slotmodule.Useoneoftheprovidedcabletiestosecurethe
MODNTX0/RX0RFcable,bothLVDScablesandthePower(PWR)cabletotheRFcable
labeled
MODNTX1/RX1,ensuringthatthecablebundlewillnotbepinchedorprevent
thePRUdoorfromclosing.