Install any 40W RF Module(s)
FlexWave Prism Host, Remote and EMS 5.1 System Reference Page 129
ADCP-77-073 • Issue 2 • 11/2009 © 2009 ADC Telecommunications, Inc.
4.4.9 Determine the Circuit Breaker or Fuse for Remote
The Prism Remote supports power input from a 90 to 240 VAC power supply as
shown below.
4.4.9.1 Power Consumption
Do the following to determine the maximum power consumption, which determines
the circuit breaker or fuse to use.
477 Review the Remote order to determine the information listed below and then use
this information to find the power consumption from Table 4-2 and Table 4-3:
• RF bandwidth?
• DART type (Classic, Single SuperDART or Dual
SuperDART)
• Diversity or Non-Diversity?
Power module
AC switch
DC switches (4)