User Manual Part 2
Installing the Remote Unit
Page 126 FlexWave Prism Host, Remote and EMS 5.1 System Reference
© 2009 ADC Telecommunications, Inc ADCP-77-073 • Issue 2 • 11/2009
Use the following procedure to install the AC power wiring:
355 Locate the AC power cable that is provided separately with the Remote.
366 Route the power cable between the AC power port, located on the underside of
the Remote and the nearest AC power junction box as shown below. It may be
necessary to install a new junction box if an existing junction box is not available.
377 Secure the cable between the AC power port and the AC power junction box per
local practice. Leave sufficient slack in the cable to allow it to be easily connected
and disconnected from the AC power port.
388 Install any AC power supply wires that may be required between the AC junction
box and the AC circuit breaker box.
The power cable is rated for indoor or outdoor use and must not be placed within
electrical conduit a
s this will impede the cooling of the cable during usage. The cable
run distance to the AC power sour
ce must not exceed 100 feet.
It is recommended that an AC outlet be installed near the Remote for powering tools
and test equipmen
t. This outlet must include a GFCI device for protection.
An appropriate disconnect device, as well as branch circuit protection, must be provided
as part of t
he installation.
Remote enclosure
77073-071
AC power junction box
AC power cable
AC power wires routed
to circuit breaker panel