User Manual Part 1

Prism System Components
Page 44 FlexWave Prism Host, Remote and EMS 5.1 System Reference
© 2009 ADC Telecommunications, Inc ADCP-77-073 Issue 211/2009
2.3.2.3 Remote Power Supply and Cable Assembly
The Remote is powered by 100 to 240 VAC (nominal 120 or 240 VAC), 50 to 60 Hz
power. The AC power is supplied through a 15-foot (4.6m) three-wire power cable
that is provided with the unit. The power cable connects to a 3-pin AC power
connector mounted on the bottom of the Remote.
The stub end of the power cable must be routed to an external junction box (not
provided) for connection to the AC power source. A circuit breaker rated at 20 Amps
(120 VAC) should be used to provide over-current protection for the Prism power
circuit. It is also recommended that an external AC outlet (not provided) be installed
near the Remote to power test equipment and tools.
The Remote model determines the number of power supplies.
The Single-Band Remote is powered by one power supply.
The Dual-Band Remote is powered by two power supplies.
The Tri- and Quad-Band Remotes are powered by three power supplies.
There are up to four switches that independently control DC power for each RF
Module. These switches are labeled MOD A, MOD B, MOD C, and MOD D and
correspond to the RF Module shelves, from bottom to top, that are labeled the same.
Figure 2-11. Remote Power Supply
For further information on calculating required power, see “Power Consumption” on
page 129.
Power module
AC switch
for Remote
DC switches (4)
labeled MOD A - MOD D
for up to 4 RF Modules
Up to three power
supply units
SeRF module will be installed
on top of the Power Supply module
77073-038