Installation Manual
Table Of Contents
- WAVEXpress/BTS Installation and Commissioning Guide
- One - Unpacking the WAVEXpress/BTS
- Two - Internal BTS Cabling and Jumpering
- Three - Installation
- 3-1 Wall Installation
- 3-2 Table Mount
- 3-3 Rack Installation
- 3-4 Common Final Installation Procedures
- 3-4.1 Connection of the Cable Gland
- 3-4.2 Connection of the Grounding Cable
- 3-4.3 Connection of the Antennas to the Bulkhead Plate
- 3-4.4 Connection of the Optional Combiner Assembly
- 3-4.5 Connection of the Power Supply
- 3-4.6 Connection of the T1 Lines
- 3-4.7 Connection to External Alarms
- 3-4.8 Optional Voltage Standing Wave Ratio (VSWR) Check
- 3-4.9 Post Installation Checks
- 3-5 Outdoor Installation
- Four - Off-Line Commissioning
- Five - Off-Line Commissioning of a Daisy Chain
- Six - Post Off-Line Commissioning
- Seven - On-Line Commissioning
- Appendix 1 - Connection of the Combiner Assembly
- Appendix 2 - BTS Field Maintenance
- A2-1 WAVEXpress/BTS Field Replacement Maintenance
- A2-1.1 Replacing the WAVEXpress/BTS IWP card
- A2-1.2 Replacing the WAVEXpress/BTS T1 card
- A2-1.3 Replacing the WAVEXpress/BTS TRX card
- A2-1.4 Replacing the WAVEXpress/BTS RF distribution card
- A2-1.5 Replacing the clock module
- A2-1.6 Replacing power supply units
- A2-1.7 Replacing fan assemblies
- A2-1.8 Replacing filters (p/n 520081-01)
- A2-1.9 Replacing the antenna bracket with a combiner assembly
- A2-1 WAVEXpress/BTS Field Replacement Maintenance
- Checklist 1 - Installation Checklist
- Checklist 2 - Commissioning Checklist
Release 3.3, Revision A 1/99
68 WAVEXpress/BTS Installation and Commissioning Guide
Procedure to Set Up an Ethernet Connection
Step 1
Connect a T-connector to each end of the RG-58 coaxial cable.
Step 2
Connect a 50-Ohm terminator to the T-connector on each end of the RG-58 coaxial cable.
Step 3
If an AUI-BNC transceiver is not already connected to the IWP’s Ethernet port labelled “ENET,” then
attach one now.
Step 4
Attach one end of the cable with the T-connector to the AUI-BNC transceiver on the IWP.
Step 5
Connect the other end of the cable to the 3Com Combo transceiver’s BNC transceiver.
Step 6
Insert the 3Com Combo transceiver firmly into the PCMCIA card slot on the left side of the Craft PC.
The following illustration shows a completed physical connection between the Craft PC and a WAVEXpress:
Figure 4-2:
Connection to the Craft PC via the Ethernet port
567
6&1
3:5
21
/,1(
)/7
&'1
(1(7
(;7
;5()
Craft PC
PCMCIA card slot
3Com Combo transceiver
RG-58 coaxial cable
Ethernet
port
IWP card
BNC T-connector
50-Ohm terminator
AUI-BNC
Transceiver
BNC T-connector
50-Ohm terminator