User Manual
Table Of Contents
- FlexWave microBTS 1 x 1 and 2 x 1 Installation and Commissioning Guide
- Chapter 1 - Introduction
- Chapter 2 - Unpacking and Inspection
- Chapter 3 - Mounting Procedures
- Chapter 4 - Installation Procedures
- 4.1 Installation Overview
- 4.1.1 Installation Hardware Provided with microBTS Enclosure
- 4.1.2 Tools and Materials Required
- 4.1.3 Ground Wire Installation
- 4.1.4 Network Listen Antenna Installation
- 4.1.5 IP Backhaul Cable Installation
- 4.1.6 Base Station Antenna Cable Installation
- 4.1.7 AC Power Wiring Installation
- 4.1.8 DC Power Wiring Installation
- 4.1.9 Touch-Up Painting
- 4.1.10 Shield Installation (option)
- 4.2 microBTS Replacement
- 4.1 Installation Overview
- Chapter 5 - microBTS Initial Configuration
FlexWave microBTS Installation and Commissioning Guide Page 33
© 2009, ADC Telecommunications, Inc.
ADCP-77-086 • Issue 2 • 04/2009 • Chapter 4 - Installation Procedures
4 Install any AC power supply wires that may be required between the AC junction box and
the AC circuit breaker box.
5 Connect the AC power cable wires to the AC power supply wires. Refer to Figure 4-6 to
identify the color code and wire designations.
6 At the AC circuit breaker box, connect the AC power supply load wires to a 15 amp circuit
breaker.
7 Place the circuit breaker in the ON position and then test the connectorized end of the AC
power cable for proper voltage levels and correct polarity.
8 When testing is complete, place the circuit breaker in the OFF position.
9 Remove the dust cap from the AC power port located on the bottom of the enclosure as
shown in Figure 4-7.
Note: The power cable is rated for indoor or outdoor use and must not be placed within electrical
conduit as this will impede the cooling of the cable during usage. The cable run distance to the AC
power source must not exceed 100 feet.
Note: It is recommended that an AC outlet be installed near the enclosure for powering tools and test
equipment. This outlet must include a GFCI device for protection.
Figure 4-6: AC Power Cable Connections
AC POWER CORD
PROVIDED WITH ENCLOSURE
BLACK
GREEN/YELLOW
WHITE
LINE
GROUND
NEUTRAL
120 VAC POWER
WIRING
AC POWER CORD
PROVIDED WITH ENCLOSURE
BLACK
GREEN/YELLOW
WHITE
LINE 1
GROUND
LINE 2
240 VAC POWER
WIRING
120 VAC CONNECTIONS
240 VAC CONNECTIONS
20778-A
CONNECTOR PIN DESIGNATIONS
PIN 1 - GREEN/YELLOW
PIN 2 - WHITE
PIN 3 - BLACK
END VIEW OF
CONNECTOR
1
2
3