Page 160 InterReach Fusion Wideband Installation, Operation, and Reference Manual
© 2015 TE Connectivity D-620616-0-20 Rev K TECP-77-044 Issue 9 March 2015
Alarm Sense
Use AdminBrowser to enable the Fusion Wideband system for “alarm sense” when connecting to
the contact closure of Unison Main Hubs or other external alarms (refer to “Set Contact Sense
Properties” in the AdminBrowser User Manual).
NOTE: This procedure assumes that the system is installed and that has been programmed with bands.
When you connect Unison to Fusion Wideband, the Fusion Wideband Main Hub is the alarm sense
(input) and the Unison is the alarm source (output), as shown in Figure 30. The input alarm sense
needs to be set to normall
y closed (NC).
Figure 30.
Using Fusion Wideband to Monitor Unison
Unison supports only faults. You must use the Alarm Sense Adapter Cable to interface the
daisy-chain cable to Fusion Wideband (see Figure 31). The adapter cable is required because it
translates the Unison fault pinout to the sense input pin
s on the Fusion Wideband Main Hub.
Figure 31.
Alarm Sense Contacts
5-port Alarm Daisy-Chain Cable
Up to 5 Unison Main Hubs
Alarm
Source
Alarm
Source
Alarm
Sense
Fusion Main Hub
Alarm Sense
Adapter Cable
+5V
8
1
External
Equipment
Contacts
Diagnostic 1