Installing a Fusion Wideband Main Hub
InterReach Fusion Wideband Installation, Operation, and Reference Manual Page 121
D-620616-0-20 Rev K TECP-77-044 Issue 9 March 2015 © 2015 TE Connectivity
Figure 18. Recommended Hub-Wire Routing
To connect DC power to a Main Hub or Expansion Hub:
1 Strip 5/8” (16mm) of wire insulatio
n material off each power wire.
2 Insert the +4
8VDC wire into the compression terminal at the “+” location.
3 Insert the -48
VDC wire into the compression terminal at the “-” location.
4 Bare wire ends should be fully inserted into terminal.
5 Use a flat blade screw driver to fasten the wire inside the compression terminal.
6 For the Protective Ground Wire, use
14AWG minimum wire with a #8-32 stud size ring lug,
as shown below.
CAUTION! The warning color code of the power cables depends on the color coding of the DC power source
installed at your site. Color code standards for DC wiring do not exist. To ensure that the correct
polarity is connected to the hubs, confirm the connection of the power cables to the + (positive)
and - (negative) leads at the power source.