User Manual
Connecting Contact Alarms to a Fusion Wideband System
7-58 InterReach Fusion Wideband Installation, Operation, and Reference Manual
CONFIDENTIAL D-620616-0-20 Rev G
7.7 Connecting Contact Alarms to a Fusion Wideband
System
The Fusion Wideband Main Hub can generate (source) two contact alarms as well as
sense three external contact alarm.
• Alarm Source (refer to Section 7.7.1 on page 7-59)
The Fusion Wideband Main Hub has two alarm contacts, fault (major) and warn-
ing (minor). These contacts are normally-closed (NC) and will open when an inter-
nal alarm is detected.
NOTE: The contact can be changed to normally-open (NO) with Admin-
Browser. This is not recommended since no alarm would be sent if power to
the Fusion Wideband Main Hub fails.
• Fault is activated when any faults or disconnects are detected.
• Warning is activated when any warning conditions are detected
except lockout or when the end-to-end system test is not valid.
• Alarm Sense (refer to Section 7.7.2 on page 7-62)
The Fusion Wideband Main Hub can monitor 3 external alarm contacts. Each port
can be configured for normally-open (NO) or normally-closed (NC) contacts. The
interface expects a set of floating contacts, and an external voltage source is not
required for this interface. Use AdminBrowser to monitor the port status.
Table 7-8 lists the alarm types, equipment to which the Fusion Wideband Main Hub
is connected, cable(s) used, and the faults and warnings that are detected.
Table 7-8 Alarm Types
Alarm
Type
Fusion
W
ideband
Connected to Cable(s) Used Errors Detected
Source FlexWave 5-port Alarm Daisy-Chain Cable Faults
Source BTS 5-port Alarm Daisy-Chain Cable Faults and Warnings
In addition, a custom daisy-chain cable-to-BTS interface
cable is required. Make this interface cable to the desired
length and with the appropriate pin placement.
Sense Unison 5-port Alarm Daisy-Chain Cable
and the
Alarm Sense Adapter
Cable
Faults
Note that FlexWave Focus supports only faults (major errors).