User's Manual Part 2

Table Of Contents
Installing Fusion Wideband
Page 120 InterReach Fusion Wideband Installation, Operation, and Reference Manual
© 2013 TE Connectivity Ltd D-620616-0-20 Rev H TECP-77-044 Issue 7 May 2013
IftheFiberJumperisColorCoded
1 Connect“b
lue”toUPLINKportsontheMainHub.
2 Connect“red”to
DOWNLINKportsontheMainHub.
3 Recordwhichcolorandportnumb
eryouconnectedtoUPLINKandDOWNLINK.
Thisinformationisneededwhenco
nnectingtheotherendofthefibercabletotheExpansion
Hub’sfiberports.
ThefiberportLEDsshould
beoff,indicatingthattheExpansionHub(s)arenotconnected.
CAUTION! Onlytrainedandqualifiedpersonnelshouldbeallowedtoinstallorreplacethisequipment.
ACPoweredMainHub
ToconnectACpowertoaMainHub:
1 ConnecttheAC
powercordtotheMainHub.
2 Plu
gthepowercordintoanACpoweroutlet.
DCPoweredMainHubandExpansionHub
CAUTION! The protective earth connection should be connected before proceeding with power
connections.ConfirmtheDCpowersourceispoweredoffduringinstallation.Damagetohubs
mayresultifpowerisconnectedimproperly.
TheDCpoweredMainHubandExpansionHubareintendedtobepoweredbya+48VDCpower
source.Thehubsaredesignedfor14AWGto6AWGwiresizeconnections.UseonlyULlisted
AWMwire,rated600Vand90degreesC.
Ifwireslargerthan6AWGareneededfromtheDCpowersource,fo
llowlocalcodesforreducing
thewiresizeathubconnectionpoint.
Followlocalcodesforroutingofpowercablestopowersource.
TheunitshouldbeconnectedtoaDCbranch
circuitbreaker.Asuitabledisconnectdevicemust
beprovidedintheDCbranch,eitheracircuitbreakerorswitch,thatcanbeemployedto
disconnectpowertothesystemduringservicing.
MakingPowerConnections