Connecting Contact Alarms to a Fusion Wideband System
7.7.2 Alarm Sense
Use AdminBrowser to enable the Fusion Wideband system for “alarm sense” when
connecting to the contact closure of Unison Main Hubs or other external alarms (refer
to Set Contact Sense Properties in the AdminBrowser User Manual).
Using Fusion Wideband to Monitor Unison
When you connect Unison to Fusion Wideband, the Fusion Wideband Main Hub is
the input of the alarms (alarm sense) and the Unison is the output (alarm source), as
shown in Figure 7-33. The input alarm sense needs to be set to normally closed (NC).
Figure 7-33 Using Fusion Wideband to Monitor Unison
Unison supports only faults. You must use the Alarm Sense Adapter Cable (refer to
page 7-60) to interface the daisy-chain cable to Fusion Wideband. The adapter cable
is required because it translates the Unison fault pinout to the sense input pins on the
Fusion Wideband Main Hub.
Up to 5 Unison Main Hubs
Fusion Wideband Main Hub
Alarm
Sense
Alarm
Source
Alarm
Source
Alarm Sense
Adapter Cable
5-port Alarm Daisy-Chain Cable
Band 1
Band 2
Band 3
UL1 UL2
UL3
DL1
DL2
DL3
AC Power
Alarms