User Manual
ADCP-75-150 • Preliminary Issue A • March 2003 • Section 3: Host Unit Installation
Page 3-15
©
2003,
ADC
Telecommunications,
Inc.
10 EXTERNAL ALARM SYSTEM CONNECTIONS
The
alarm
interface
between
the
HU
and
an
external
alarm
system
is
supported
by
a
six-terminal
plug
(with
screw-type
terminals)
that
connects
to
a
receptacle
mounted
on
the
HU
front
panel.
The
terminal
plug
provides
connections
to
normally
open
(NO)
and
normally
closed
(NC)
dry
type
alarm
contacts
for
both
major
and
minor
alarms.
A
category
3
or
5
cable
is
typically
used
to
connect
the
HU
to
the
external
alarm
system.
Use
the
following
procedure
to
install
the
alarm
wiring
and
connect
it
to
the
HU:
1. Obtain
the
required
length
of
category
3
or
5
cable.
2. Route
the
cable
between
the
HU
and
the
external
alarm
system
(if
not
already
routed)
and
then
cut
to
the
required
length.
Allow
sufficient
slack
for
dressing
and
organizing
the
cable
at
the
HU.
3. Strip
back
the
outer
cable
sheath
and
insulation
to
expose
the
wires
at
both
ends
of
the
cable
and
strip
back
0.2
inches
(5
mm)
of
insulation
from
each
wire.
4. Connect
the
Major
alarm
wire
pair
to
the
MAJOR
COM/NC
or
MAJOR
COM/NO
terminals
(whichever
is
required
by
the
external
alarm
system)
on
the
HU
alarm
terminal
connector
(supplied
with
HU)
as
shown
in
Figure 3-14.
Figure 3-14. External Alarm System Connections
5. Connect
the
Minor
alarm
wire
pair
to
the
MINOR
COM/NC
or
MINOR
COM/NO
terminals
(whichever
is
required
by
the
external
alarm
system)
on
the
HU
alarm
terminal
connector
(see
Figure 3-14).
18660-A
ALARM
CONNECTOR
MAJOR ALARM WIRES
MINOR ALARM WIRES
ALARM CONNECTOR
DETAIL
NO
COM
NC
NO
COM
NC