User Manual

ADCP-75-192 • Issue 1 • December 2005 • Section 3: Network and System Installation and Setup
Page 3-4
2005, ADC Telecommunications, Inc.
Table 3-1. HUB Rack Numbering
CHASSIS OR SHELF HEIGHT LOCATION*
Attenuator Shelf 2U U42
PDU 2U U40
Ethernet Hub 1U U38
Digital Chassis (top) 4U U37
BIM 1U U33
RF Chassis (top) 4U U32
BIM 1U U28
Digital Chassis (top) 4U U27
BIM 1U U23
RF Chassis (top) 4U U22
BIM 1U U18
Digital Chassis (top) 4U U17
BIM 1U U13
RF Chassis (top) 4U U12
BIM 1U U8
Reference Module (bottom) 1U U7
*’U’ numbers are printed on the rack rails of the OP-HUB2 rack.
Hub Racks are numbered sequentially, Rack1, Rack2, etc, or by serial number.
Chassis in Hub racks are numbered by ‘U’ number. For example, the lowest RF
chassis shown in Table 3-1 would be numbered U12.
BIMs in racks are numbered by ‘U’ number. For example, the lowest BIM shown in
Table 3-1 Would be numbered U8.
Power Attenuators are located at the top of the Hub rack or mounted to a wall.
WSP Base stations should be given unique Tenant Name and BTS ID designations.
Each base station sector is cabled to a separate attenuator and BIM unit in the Hub
rack.
Ensure that RF cables from the BIM forward output ports are connected to FBHDC
modules in its related HUB RF chassis (not used if BTS is directly cabled to FBHDC)
Ensure that RF cables from the BIM reverse input ports are connected to HUC
modules (primary to primary and diversity to diversity (if diversity is used)). Ensure
that any HUC and FBHDC modules connected to a given BIM must reside in the same
Hub RF chassis.