PROCESS binary inputs:
+BIN1 binary input No. 1, positive pole, supply max. DC 30 V / 4 mA,
+BIN2 binary input No. 2, positive pole, supply max. DC 30 V / 4 mA,
-BIN12 binary inputs No. 1 and 2, negative pole,
+BIN3 binary input No. 3, positive pole, supply max. DC 30 V / 4 mA,
+BIN4 binary input No. 4, positive pole, supply max. DC 30 V / 4 mA,
-BIN34 binary inputs No. 3 and 4, negative pole.
RELAY OK change-over contact of the OK relay:
NC signal under the limit of alarms,
COM common contact,
CN complementary NC closed at rest.
RELAY ALERT change-over contact of the ALERT relay:
NC signal exceeded the ALERT limit,
COM common contact,
CN complementary NC closed at rest.
RELAY DANGER change-over contact of the DANGER relay:
NC signal exceeded the DANGER limit,
COM common contact,
CN complementary NC closed at rest.
RELAY SYSTEM change-over contact of the SYSTEM relay:
NC system functions, vibration sensor connected,
COM common contact,
CN complementary NC closed at rest.
LOOP1 ´LF´ 4 – 20 mA output current loop of the measured value for the LF (ISO) signal:
+LOOP loop positive pole, supply max. DC 30 V,
- LOOP loop negative pole.
LOOP2
4 – 20 mA output current loop of the measured value for the bearing condition signal:
+LOOP loop positive pole, supply max. DC 30 V,
- LOOP loop negative pole.
Power supply unit separate power supply unit 24 V / 80 mA (per order only):
+24V power supply unit positive pole,
0V 0 V of the power supply unit.