Archiving of Measured Data
The Adash 3600 set can be extended with the Adash 3600-MEM memory module, which archives
measured data on the flash card with a capacity of 16 MB to 128 MB. The flash card with the
measured data can be removed from the module at any time and the archived data can be imported to
the DDS 2000 user software by Adash for further processing.
For the systems with on-line network transmission of the measured data, all the on-line data are
stored on the flash card that were not transmitted via network to the host PC and were overwritten with
new data in the memory of the Adash 3600-NET module. In the set without the Adash 3600-MEM
memory module the old on-line data would be lost. If the host PC is not continuously in operation but
the user wants to archive all the on-line data, the Adash 3600 set must use the memory module.
Alarm Limits Signalling
The multi-channel Adash 3600 set can be extended with 1 to 8 Adash 3600-REL relay outputs
modules for the signalling of alarm limits overload of individual vibration sensors. Each Adash 3600-
REL module is mounted with up to eight relay pairs. Each pair can be appropriately programmed so
that it signals, by the close/open combination, three states: OK, ALERT and DANGER.
The assignment of a relay group to a sensor and the programming of the group behaviour for each of
the three signalled states is carried out via the Adash 3600 Setup program.
Current Loops 4 - 20 mA
The basic Adash 3600 set has two current loops 4 – 20 mA for measured data output. By mounting 1
to 8 Adash 3600-LOOPS modules, their number can be significantly increased. Each Adash 3600-
LOOPS module has 8 or 16 programmable current loops 4 – 20 mA for measured data output. In
addition, each current loop of the Adash 3600-LOOPS module is able to display error conditions of
measurement by output currents 3.5 mA, 3.75 mA, 22 mA and 24 mA.
The assignment of the current loop to the measurement, the setting of the measured data range for
display by output current 4 – 20 mA and the assignment of output currents to error conditions is
performed via the Adash 3600 Setup program.