Setting of alarm by binary inputs
Choose radio-button By bin inputs in the MPX - Channel window and define group of alarm limits for
used binary input. Alarm limits will depend on the active binary input. If more binary inputs are active,
then leftmost active binary input has priority.
Measure triggering by binary inputs
Measuring on the input channel of the A3600 can be triggered by binary inputs (BIN1 - BIN3). This
setting is available only in the Service mode (Mode - Change mode - password: 456654) of
A3600Setup. Click on the button Trigger and select binary input, which will be trigger a measuring.
The measuring will start only if selected binary input is active. Binary input must be active all the
measuring time. If this function is used, then blinks T control LED on the front panel of the A3600MAIN
module.
setting of alarm limits
by binary inputs