Another approach might be to choose a more powerful UPS, which will guarantee
a few hours of battery power. When using this approach, your software must be
able to initiate shutdown when a certain battery level is reached. The PowerChute
plus
software delivered by your APC UPS supports this feature of system
shutdown. If you installed the Interface Expander in your APC UPS you can
control three systems in this way by connecting them to serial ports on the UPS.
Table 3 shows you the on-battery time for selected server models.
Table 3. On-Battery Run Time for Selected Server Models
2.2.3 Installing the APC UPS
First, you must install the
UPS Interface Expander
accessory. The Interface
Expander provides two additional RS232 computer interface ports. Install it in the
SmartSlot in your APC UPS. As your UPS has one RS232 interface port you can
now provide a safe system shutdown for up to three servers.
The two serial interfaces on the Interface Expander are
Basic Monitoring Ports,
which means they report basic power status conditions such as
on-battery
,
low-battery
and
return of line power
to the attached devices. This is sufficient to
control your systems if a power fail condition appears. Later you must install the
800- 9 151133
900 - 7 12 9 29
1000 - 6 11 8 26
1200 - - 8 6 20
1400 - - 7 5 16
1600 - - - - 13
2000----9
2200----8
2500----6
3000----4
Model Run-time
Load
SU700NET SU1000NET SU1400NET SU1400RMB SU3000RMB
PC Server 325
Pentium Pro
265 VA 25 min. 42 min. 68 min. 49 min. 110 min.
PC Server 325
Pentium II
280 VA 23 min. 40 min. 64 min. 50 min. 105 min.
PC Server 330
Pentium II/PRO
300 VA 20 min. 36 min. 57 min. - -
Netfinity 7000 490 VA - - 31 min 23 min. 60 min.
Note: Stated run times and power are for typical configurations (70% of maximum capacity).
VA LOAD SU700NET SU1000NET SU1400 NET SU1400RMB SU3000RMB
Note: Your needed on-battery run time depends on the time for your shutdown procedure.