Specification Sheet
OPTIONS & ACCESSORIES FOR EXIT DEVICES
Options &
Accessories
for Exit Devices
Electric Latch Retraction
The EL option for rim exit devices and LR option for all other
exit devices (non-rim exit devices) use a solenoid mounted
in pushbar for instantaneous unlocking and locking of the
exit device from a remote location or access control device.
Because electrical operation of device is fail-secure, this option
can be used on fire-rated as well as life-safety applications. In
the event of a power failure, device automatically relocks. Rim
devices with the EL option are available in 12 or 24 VDC, and
can be powered with a simple transformer and rectifier or other
DC power supply.
SOLENOID SPECIFICATIONS FOR CVR, SVR,
AND MORTISE TYPE DEVICES (LR OPTION):
16 Amps inrush/ 0.5 Amps hold
SOLENOID SPECIFICATIONS FOR RIM DEVICES
(EL OPTION):
EL-12 VDC – 1.5 Amps inrush/hold
EL-24 VDC – 0.6 Amps inrush/hold
Solenoids are rated for both intermittent and continuous
operation. Only rim exit devices with the “EL” application are
available with mechanical dogging, specify “ELD”
Order PS-LR Power Supply separately for LR option (PS-LR
powers two exit devices). For warranty purposes Adams Rite
requires that all CVR, SVR, and Mortise type exit devices with
the LR option be paired with PS-LR power supplies. Rated for
continuous duty (see POWER).
Order PS-1 Power Supply separately for EL option
(PS-1 powers two exit devices). Rated for continuous duty
(see POWER).
4612 Power Transfer is available separately for secure and
unobtrusive means of channeling electrical wiring from the door
frame into the door itself.
Alarmed Exit Device
For all Adams Rite Exit Devices
This battery-operated option emits a loud (95 decibel) alarm to
notify management of unauthorized exit. Alarm is controlled by
a key in any standard Mortise cylinder with MS
®
cam to arm,
disarm, delay, or reset the alarm. Will not alter the Life-Safety
characteristics of the exit device in any way. Red letters printed
on the bar give a “hands off” warning to deter accidental
activation. Four AA alkaline batteries power twin horns for two
minutes (or until disarmed) when pushbar is depressed. Beeps
to signal need for new batteries. Minimum opening width: 36"
Silent Electrification Motorized
Latch Retraction
The SE Motorized Latch Retraction option provides near-silent operation for quiet
environments such as hospitals, offices, hotels, and libraries where solenoid-driven
devices would be disruptive. The high speed/low current draw motor (0.4 Amps
inrush current, 0.2 Amps hold current) offers a powerful yet efficient system that
allows for lighter gauge wiring and an energy-saving reduced amperage power
supply. The device also features electric latch retraction with electric dogging which
minimizes hardware projection and noise. The SE option is available with 3000/8000
Series Exit Devices and the RITE Door
®
.
Order PS-SE Power Supply separately (PS-SE powers two exit devices). Rated
for continuous duty (see POWER). Adams Rite requires that for optimal
performance all exit devices with the SE option be paired with PS-SE
power supplies. Failure to do so may cause permanent damage to the
exit device and will void the Manufacturer’s warranty.
4612 Power Transfer is available separately for secure and unobtrusive means of
channeling electrical wiring from the door frame into the door itself.
Adams Rite Exit Devices can be ordered with electrification
options for standalone access control or integration with
maglocks, card readers, keypads, fire alarms, power door
operators, and other control systems. Different exit device
types have different installation and power requirements.
Please refer to product pages for more information on
all available exit device types, functions, installation
requirements and complete How-to-Order guides.
EXIT DEVICES
ED-19
800.872.3267 • Fax 800.232.7329
10027 S. 51st Street, Ste 102
Phoenix, Arizona 85044
www.adamsrite.com
ARM-014-9/14