Technical data

TECHNICAL AND INSTALLATION
10
7. PERFORMANCE
Performances
Type
Peak output
(l/10min)
1
st
hour output
(ltrs/60min)
Continuous output
(ltrs/hr)
Boiler
Output
(kW)*
Primary
flow rate
(ltrs/hr)
Heat up time
10°C–85°C
(min)
40°C 45°C 60°C 40°C 45°C 60°C 40°C 45°C 60°C
SLE 130 236 202 117 784 672 384 658 564 320 23 2100 22
SLE 160 321 275 161 1063 911 549 890 763 465 31 2600 22
SLE 210 406 348 209 1349 1156 689 1132 970 576 39 3500 20
SLE 240 547 469 272 1820 1560 913 1527 1309 769 53 4200 20
SLE 300 700 600 337 2319 1988 1165 1943 1665 994 66 5300 20
Operating conditions: primary fluid 85°C
cold inlet 10°C
* The boiler outputs shown are the minimum to provide the domestic performance figures
detailed. Should a lower capacity boiler be used the performance will be reduced.