Operating Instructions and Installation Instructions

9
EN
BURNER FEATURES
ACV BMV1 AND BMV2 OIL BURNERS
Description
For the Delta Performance oil-fuelled balanced flue model, we have
opted for the all-new technology of the ACV BMV1 and BMV2 oil
burner, manufactured from high quality components combining
performance with perfect combustion.
CO2 chart for the ACV BMV1 and BMV2 burner
ACV BMV1 AND BMV2
BURNER FACTORY SETTINGS
FV/35 FV/50
Burner BMV1 BMV2
Input kW 34.9 50
Nozzle gal/h 0,75 1.25
Nozzle angle 60°H 60°H
Oil flow Kg/h 2.95 4.22
Pump pressure bar 11.8 9.5
Flue gas index 0 - 0.5 0 - 0.5
Air reducer % 37 60
Air inlet % 90 90
Nozzle line pressure mbar 3.5 - 4 3.5 - 4
Nozzle line mm 10 10
Weight Kg 14.5 14.5
14 %
13,5 %
13 %
12,5 %
12 %
-10 0 10 203040
% CO2
Outside temperature
ACV BMV1 AND BMV2 BURNER CAPTIONS
(see illustration O)
1. Control unit
2. Nozzle line protection
3. Warning lamp
4. Electric plug connector
5. Attachment bracket
6. Burner blast tube
7. Ignition unit
8. High tension ignition cable
9. Oil pump
10. Oil aspiration line connection
(circuit with return only)
11. Oil return connection
12. Motor condenser
13. Motor
14. Pump / nozzle connecting pipe
15. Burner casing
16. Nozzle line adjustment screw
WARNING: Set the % of CO
2 as per the data in the diagram above