MAINTENANCE
PERIODIC BOILER MAINTENANCE TASKS
Tasks
Frequency
Periodic
inspection
1
year
2
years
End-user Professional
1. Make sure that the system water pressure is at least 1 bar
when cold. Top up the system if necessary, adding small
quantities of water at a time. In case of repeated lls, call
your installer.
X X
2. Check that there is no water on the oor in front of the
boiler. Call your installer if there is.
X X
3. Check the presence of a ame through the ame sight
glass. If there is no ame, see the burner manual.
X X
4. Check that the charging pump is running by placing a
hand on it.
X
5. Check the correct operation of all thermostats and safety
devices: boiler thermostat, safety thermostat, safety valves,
etc.
X
6. Check that the the oil connections are tight and there is
no leak, that the hoses are not kinked and that there is not
entrance of air in the circuit.
X
7. Check that all hydraulic and electrical connections are
correctly fastened and tight.
X
8. Check the ue gas exhaust: correct fastening, correct
installation, no leaks or clogging.
X
9. Check the combustion parameters (CO and CO2), see
"Combustion adjustment", page 33
X
10. Clean the burner and the heating body, see "Cleaning the
burner and the heating body", page 36 and the burner
manual.
X
11. Check the cleanliness of the condensate trap. If it is
very dirty, rst clean the condenser, see "Cleaning the
condenser", page 36, then the condensate trap, see
"Cleaning the condensate trap", page 37.
X
12. Clean the condenser, see "Cleaning the condenser", page
36.
X
13. Clean the condensate trap, see "Cleaning the condensate
trap", page 37.
X