User's Guide

Guia de usuário Edge-30R+ Autoid / Edge-30R-N+ Autoid
Rev. 13
Copyright © 2022 Acura Technologies
91 de 92
is properly made according to the Electrical Connections - Ethernet Network;
4. Make sure that the two RJ45 connectors on the reader cable are connected to the PCI Interface
and
in the correct order, connector "COMMAND READER" - black cable and connector "READER
ETHERNET" blue cape;
5. Check that the "LINK" LED of the PCI Interface is lit, if it is off, check the
network cable connection on switch/router/computer side;
6. Make sure that the computer you are trying to access the reader with has the same
network ID that reader;
15.4 In trigger mode, the input signal is not being activated by the
sensor
1. Check the datasheet of the sensor if it has output of type "dry contact" or "NPN" or
"PNP" and whether the connections made to the reader correspond to the sensor output type.
Please
refer to Electrical Connections - Digital Input for further explanations about connections;
2. If the sensor output is "dry contact", connect it to "ISO GND" and "ISO IN";
3. If the sensor output is of type "NPN" or "PNP", connect it to "ISO COM" and "ISO IN" and
check that the sensor follows the logical levels set by the reader, as described in
Electrical connections - Digital Input;
4. Finally, check on the web page of the reader if the parameter time "Filter time deboucing
trigger signal" is set correctly for the sensor used.
15.5 The Reader is not reading tags
1. Check the reader's web page for the chosen "Reading Mode";
2. Check the reader's web page to see if the value of the "Filter by tag signal level" is too
the reader to filter all tag readings. To check that you are
filtering at the time of reading, please check the Syslog messages.