Technical data
Diagnosis
Operating Manual
97ID 442281.00
WE KEEP THINGS MOVING
13
13.3.28 72:Brake test
Resolution Level Response Fault counter
For active brake manage-
ment in the SDS 5000, the 
time set in B311 has 
elapsed without the B300 
Brake test  action having 
been performed.
Message until the time set 
in B311Timeout for brake 
testB300 has elapsed twice 
and afterwards a malfunc-
tion occurs.
This malfunction only occurs with the enable 
switched off. 
Z72
Cause Description Measure Acknowledgement
1:B311Timeout The time entered in B311 Timeout for 
brake test B300 has elapsed twice 
without the B300 Brake test  action 
having been performed.
Perform the B300 Brake test action. For the Malfunction level, the 
event can be acknowledged 
for a duration of 5 minutes to 
be able to perform the B300 
Brake test  action. If this time 
elapses without the B300 
Brake test  action being suc-
cessfully performed, the in-
verter changes to the 
Malfunction state again. If the 
B300 Brake test action is suc-
cessfully performed, the event 
is automatically acknowl-
edged.
2:brakeDefective When performing the brake test ac-
tion, the holding torque entered in 
B304 or B305 could not be applied or 
the encoder test run included in the 
brake test was completed with errors.
• Perform the brake grinding func-
tion and then the brake test.
• The motor must be sent in for re-
pair. Please contact our service 
department, see section 1.4 Fur-
ther support