Technical data

Diagnosis
Operating Manual
93ID 442281.00
WE KEEP THINGS MOVING
13
13.3.25 69:Motor connect.
Resolution Level Response Fault counter
Motor connection error Can be parameterized as
inactive or malfunction in
U12
The parameterized malfunction reaction in the
A29 parameter.
Z69
Cause Description Measure Acknowledgement
1:motorNotDiscon The protection did not open during
the axis change. This cause can only
be determined when at least two
phases stick and the intermediate cir-
cuit is loaded (see E03).
Replace the protection. Switch the device on/off or
programmed acknowledge-
ment
2:no motor Possibly no motor connected or the
line to the motor is interrupted.
Check the connection of the motor.