Technical data
Diagnosis
Operating Manual
90ID 442281.00
WE KEEP THINGS MOVING
13
13.3.20 57:Runtime usage
Resolution Level Response Fault counter
The cycle time of a real time cycle was
exceeded.
Malfunction The parameterized malfunction reaction in the
A29 parameter.
Z57
Cause Description Measure Acknowledgement
2:RT2 Cycle time of real time task 2 exceed-
ed (1 ms).
The inverter must be sent in for re-
pair. Please contact our service de-
partment, see section 1.4 Further
support
Switch the device on/off or
programmed acknowledge-
ment
3:RT3 Cycle time of real time task 3 exceed-
ed (technology task).
Set a higher cycle time in A150.
4:RT4 Cycle time of real time task 4 exceed-
ed (32 ms).
5:RT5 Cycle time of real time task 5 exceed-
ed (256 ms).