Technical data
Diagnosis
Operating Manual
88ID 442281.00
WE KEEP THINGS MOVING
13
9:ECS5000failure ECS 5000 was detected, installed 
and failed.
• Uninstall and reinstall the option.
• Replace the option.
Switch the device on/off or 
programmed acknowledge-
ment
10:24Vfailure Failure of 24V supply for XEA 5001 
or LEA 5000.
Check and, if necessary, correct the 
24V supply of the option.
Switch device off/on 
11:SEA5001failure SEA 5001 was detected, installed 
and failed.
• Uninstall and reinstall the option.
• Replace the option.
Switch the device on/off or 
programmed acknowledge-
ment
12:REA5001failure REA 5001 was detected, installed 
and failed.
• Uninstall and reinstall the option.
• Replace the option.
Switch the device on/off or 
programmed acknowledge-
ment
13:PN5000 Failure1 PN 5000 was detected, installed and 
failed. Basic hardware tests have de-
tected an error.
• Check whether the PN 5000 ac-
cessory was correctly installed.
• Check whether suitable EMC 
measures were taken.
• Check whether only PROFINET-
certified components were con-
nected to the inverter.
• Check whether the cabeling and 
connections correspond to the 
PROFINET standard.
• Contact the service department, 
see section 1.4 Further support.
Switch device off/on 
14:PN5000 failure2 PN 5000 was detected, installed and 
failed. Basic software tests have de-
tected an error.
Switch device off/on 
15:PN5000 failure3 PN 5000 was detected, installed and 
failed. The watchdog function of the 
PN-5000 monitoring system has de-
tected an error.
Switch device off/on 
17:opt.2 too old for SDS 5000: Option board with old 
hardware version (XEA 5001: from 
HW 10, REA 5000: from HW 19)
• Install the projected option.
• Adjust the projection.
Switch device off/on 
Cause Description Measure Acknowledgement