13.3.18 55:OptionBoard
Resolution Level Response Fault counter
Error when operating with option board. Malfunction The parameterized malfunction reaction in the 
A29 parameter.
Z55
Cause Description Measure Acknowledgement
1:CAN5000Failure CAN 5000 was detected, installed 
and failed.
• Uninstall and reinstall the option.
• Replace the option.
Switch the device on/off or 
programmed acknowledge-
ment
2:DP5000Failure DP 5000 was detected, installed and 
failed.
3:REA5000Failure REA 5000 was detected, installed 
and failed.
4:SEA5000failure SEA 5000 was detected, installed 
and failed.
5:XEA5000Failure XEA 5000 or XEA 5001 was detect-
ed, installed and failed.
6:InkSim-Init Incremental encoder simulation on 
XEA could not be initialized. The mo-
tor may have rotated during initializa-
tion.
7:wrongOption incorrect or missing option board 
(seeE54/E58 with E68/E69) 
• Install the projected option.
• Adjust the projection.
Switch device off/on 
8:LEA5000failure LEA 5000 was detected, installed 
and failed.
• Uninstall and reinstall the option.
• Replace the option.
Switch the device on/off or 
programmed acknowledge-
ment