13.3.17 52:Communication
Resolution Level Response Fault counter
Communication malfunction Malfunction Z52
Cause Description Measure Acknowledgement
1:CAN LifeGuard The device detects the Life-Guarding 
event (master no longer sends any 
Remote Transmit Request).
Check the CANOpen master. Switch off/on the Esc key of 
the device at the front of the in-
verter or rising flank of the en-
able signal or programmed 
acknowledgement
2:CAN Sync Error Sync message was not received 
within the timeout period that is cal-
culated from the A201 Cycle Period 
Timeout as follows:
• A201≤20 ms:  
Timeout period = A201 * 4,
•20 ms < A201≤ 200 ms:  
Timeout period = A201 * 3,
• else: Timeout period = A201 * 2
• Make sure that the A201 param-
eter is correctly set.
• Make sure that the master sends 
the sync message reliably.
Switch off/on the Esc key of 
the device at the front of the in-
verter or rising flank of the en-
able signal or programmed 
acknowledgement
3:CAN Bus Off The CAN controller in the inverter 
has switched off due to critical and 
repeated CAN bit timing errors. The 
CAN controller is restarted after a 
waiting time of 2 s and acknowledge-
ment of the malfunction.
• Make sure that the CAN baud 
rate was correctly set.
• Check the wiring
• Check the bit timing of a different 
CAN subscriber.
Switch off/on the Esc key of 
the device at the front of the in-
verter or rising flank of the en-
able signal or programmed 
acknowledgement