Technical data
Diagnosis
Operating Manual
82ID 442281.00
WE KEEP THINGS MOVING
13
13.3.16 47:TorqueLimit
Resolution Level Response Fault counter
The maximum torque permitted for static 
operation is exceeded in the control 
types of servo control, vector control or 
sensorless vector control (E62 act. pos. 
T-max, E66 act. neg. T-max). Note that 
in many cases, operation at the torque 
limit is desirable.
Can be pa-
rameterized in 
U20 and U21
The parameterized malfunction reaction in the 
A29 parameter.
Z47
Possible cause Test Measure Acknowledgement
Incorrect parameteriza-
tion
Check whether the torque moments 
in E62 and E66 correspond with your 
projection.
Correct the setting of the parameters 
in C03, C05, C06, C130 and C230.
Can be acknowledged for mal-
function level by switching the 
device off/on or programmed 
acknowledgement.
Drive overloaded Check the load situation of your 
drive.
Rectify any existing blockages.