Technical data

Diagnosis
Operating Manual
75ID 442281.00
WE KEEP THINGS MOVING
13
13.3.9 39:TempDev i2t
Resolution Level Response Fault counter
The i2t model for the invert-
er exceeds 100 % thermal
overload.
Inactive, message, warn-
ing or malfunction can be
parameterized in U02
When triggering an event, a current limit initially
takes place in the servo and vector control control
types. At the same time, a fast stop is triggered as
a malfunction when parameterizing in U02. Re-
ducing the current can cause the fast stop to no
longer perform correctly.
Z39
Possible cause Test Measure Acknowledgement
Inverter overloaded Check the load situation of your
drive.
Correct the design of the drive.
Check the maintenance condi-
tion of the drive (block, lubrica-
tion, etc.)
Switch the device on/off
or programmed ac-
knowledgement
Cycle frequency too
high (B24)
Check the load situation of your drive
under consideration of the derating.
Reduce B24.
Use a drive with a suitable power
rating.