13.3.9 39:TempDev i2t
Resolution Level Response Fault counter
The i2t model for the invert-
er exceeds 100 % thermal
overload.
Inactive, message, warn-
ing or malfunction can be
parameterized in U02
When triggering an event, a current limit initially
takes place in the servo and vector control control
types. At the same time, a fast stop is triggered as
a malfunction when parameterizing in U02. Re-
ducing the current can cause the fast stop to no
longer perform correctly.
Z39
Possible cause Test Measure Acknowledgement
Inverter overloaded Check the load situation of your
drive.
• Correct the design of the drive.
• Check the maintenance condi-
tion of the drive (block, lubrica-
tion, etc.)
Switch the device on/off
or programmed ac-
knowledgement
Cycle frequency too
high (B24)
Check the load situation of your drive
under consideration of the derating.
• Reduce B24.
• Use a drive with a suitable power
rating.