Technical data
Diagnosis
Operating Manual
74ID 442281.00
WE KEEP THINGS MOVING
13
13.3.8 38:TempDev.sens
35:battery empty When switching on the inverter, it
was determined that the voltage
of the battery has fallen below the
minimal voltage of the encoder.
Referencing of the axis has been
deleted. The backup battery is no
longer able to retain the position
in the encoder over the time dur-
ing which the inverter in switched
off.
• Referencing the axis.
• Replace the AES battery before the next time the in-
verter is switched off. Note also the Absolute Encod-
er Support AES operating instructions (see section
1.3 Other manuals).
programmed ac-
knowledgement
Cause Description Measure Acknowledge-
ment
Resolution Level Response Fault counter
The temperature measured by the device
sensor exceeds the permitted maximum
value or has fallen below the permitted min-
imum value. The permitted temperatures
are saved in the power stage of the inverter.
Malfunc-
tion
The parameterized malfunction reaction in the
A29 parameter.
Z38
Possible cause Test Measure Acknowledgement
The ambient/control
cabinet temperatures
are too high or too low.
Correct the ambient temperature of
the inverter.
Take suitable measures to match the
ambient temperature to the operating
conditions of the inverter.
Switch the device on/off
or programmed ac-
knowledgement
Fan faulty Switch on the control part power sup-
ply and check whether the fan(s)
start up.
Please contact our service depart-
ment, see section 1.4 Further sup-
port