Technical data

Diagnosis
Operating Manual
71ID 442281.00
WE KEEP THINGS MOVING
13
17:X140-wire break A wire break was detected at
X120.
Check the connected cable (encoder or SSI connec-
tion).
Check the power supply of the SSI encoder or the
source that simulates the SSI signals.
Make sure that the settings of the SSI master are
matched to the SSI encoder or the source that simu-
lates the SSI signals.
Check whether a device is correctly parameterized
as the source of the SSL signals in the SSI Motion-
bus.
Check whether the devices in the SSI Motionbus
boot up together.
programmed ac-
knowledgement
18:X120-Timeout No cycle signal was detected
from the SSI master.
Check the connected cable.
Check the power supply of the SSI master.
Make sure that the settings of all devices in the SSI
Motionbus are matched to each other.
Check whether a device is correctly parameterized
as the SSL master in the SSI Motionbus.
Check whether the devices in the SSI Motionbus
boot up together.
programmed ac-
knowledgement
19:X4 double tr. Different positions are frequently
determined at X4 during dual
transfer.
Check the connection and shielding of the encoder
cable.
Reduce the electromagnetic interference.
programmed ac-
knowledgement
20:X4-Busy Encoder has not responded for
too long.
Check the encoder cable
Check whether a suitable encoder is connected.
Please contact our service department, see section
1.4 Further support
programmed ac-
knowledgement