A00 Save values
When you activate A00.0, the inverter's current configuration and the parameter 
values are stored in Paramodule, safe from loss due to a power failure. After pow-
er-off, the inverter starts with the configuration stored in Paramodule.
When it is determined during the saving procedure that the configuration data in 
Paramodule and the inverter are identical, only the parameters are stored. This 
speeds up the procedure.
You can read the following results from the third element (A00.2):
0: error free
10: write error
11: invalid data
12: write error
14: Warning
With the results 10 to 12 an error was determined while saving to Paramodule. If 
the results occur repeatedly, the Paramodule should be replaced.
Result 14 means that saving was error-free. At the same time it is determined that 
the maximum number of write cycles has been reached. The Paramodule should 
be replaced as soon as possible (MDS 5000/SDS 5000: ID 49315; FDS 5000: ID 
49314).
A37 Reset memorized values
The action A37 resets memorized values E33 to E38. The action can be started 
in A37.0.
The action offers the following result (A37.2): 0:error free.
Information
Do not turn off the power of the control section (devices of the /L ver-
sion: 24 V, devices of the /H version: supply voltage) while the action is 
still being executed. Turning off the power while actions are being exe-
cuted will cause data to be lost. The display indicates the fault *Config-
StartERROR parameters lost" or *Paramodul ERROR - Read error. In 
such cases, the application must be transferred to the inverter again 
(POSITool or Paramodul).