Technical data
3
Commissioning an inverter
ID 442281.00
WE KEEP THINGS MOVING
Operating Manual
22
3 Ready for switchon Æ Switched on Enable on high level (E19 Bit 0 = 1) and command Switch
On (A577)
4 Switched on Æ Operation enabled Enable on high level (E19 Bit 0 = 1) and command Enable
Operation (A577)
5 Operation enabled Æ Switched on Enable on high level (E19 Bit 0 = 1) and command Disable
Operation (A577)
6 Switched on Æ Ready for switchon Enable on high level (E19 Bit 0 = 1) and command Shut-
down (A577)
7 Ready for switchon Æ Switchon disable • Enable on low level (E19 Bit 0 = 0) or
• Command Quickstop (A577) or
• Command Disable Voltage (A577) or
• The ASP 5001 option (safe torque off) is active (E67).
8 Operation enabled Æ Ready for switchon Command Shutdown
9 Operation enabled Æ Switchon disable • Enable on low level (E19 Bit 0 = 0) or
• Command Disable Voltage (A577) or
• The ASP 5001 option (safe torque off) is active (E67).
10 Switched on Æ Switchon disable • Enable on low level (E19 Bit 0 = 0) or
• Command Quickstop (A577) or
• Command Disable Voltage (A577) or
• The ASP 5001 option (safe torque off) is active (E67).
11 Operation enabled Æ Quick stop Command Quickstop (A577)
12 Quick stop Æ Switchon disable • Quick stop finished or
• Command Disable Voltage (A577)
13 All states Æ Fault reaction active Fault detected
14 Fault reaction active Æ Fault Fault reaction concluded
15 Fault Æ Switchon disable Command Fault Reset (positive edge) (A577).
Change in State Conditions