Technical data
Commissioning an inverter
Operating Manual
ID 442281.00
WE KEEP THINGS MOVING
19
3
7 Operation enabled Æ Quick stop active • Quick stop signal on high level (A302) or
• Enable on low level (E19 Bit 0 = 0 or A300 = 0) and 
quick stop with enable off signal active (A44)
8 Quick stop active Æ Operation enabled Enable for high level (E19 Bit 0 = 1 and A300 = 1) and quick 
stop signal on low level (A302) and quick stop end reached 
(A45) in accordance with parameterization.
9 Quick stop active Æ Ready for switchon Enable for low level (E19 Bit 0 = 0 or A300 = 0) and quick 
stop end reached in accordance with parameterization 
(A45).
10 Quick stop active Æ Switchon disable The ASP 5001 option (safe torque off) is active (E67).
11 Operation enabled Æ Rea Enable for low level (E19 Bit 0 = 0 or A300 = 0) and quick 
stopwith enable off inactive (A44).
12 Operation enabled Æ Einschaltsperre The ASP 5001 option (safe torque off) is active (E67).
13 Switched on Æ Switchon disable • DC link not charged or
• The ASP 5001 option (safe torque off) is active (E67).
14 All states Æ Störungsreaktion Aktiv Fault detected (E81).
15 Fault reaction active Æ Fault Fault reaction concluded (E81).
16 Fault Æ Switchon disable No fault is queued (E81) and rising edge of the acknowl-
edgment signal (A301).
Zustandswechsel Bedingungen