The following eight states exist in the standard device state machine in accor-
dance with the DRIVECOM profile for drive technology.
Display  Designation Behavior
Or
Not ready to 
switch on
• The electronics are powered.
• Self-test is running.
• Initialization is running.
• Drive function
a)
 is disabled.
• Ready-for-operation relay is open.
Switchon disable • Software/hardware initialization is finished.
• The application was reparameterizedn.
• The drive function
1
 is disabled.
• The ready-for operation relay is closed.
• The ASP 5001 option (safe torque off) is active.
Ready to switch 
on
• The application can be reparameterized.
• The drive function
1
 is disabled.
• The ready-for-operation relay is closed.
Switched on • The application can be reparameterized.
• The drive function
1
 is disabled.
• The ready-for-operation relay is closed.
Operation  
enabled
• The application can be partially parameterized.
• The drive function
1
 is enabled.
• The ready-for-operation relay is closed.
Fault • The application can be partially parameterized.
• The drive function
1
 is disabled.
• The ready-for-operation relay is closed.
Fault reaction  
active
• The application can be reparameterized.
• An error-dependent action is being executed (dis-
able drive function or quick stop).
• The drive function
1
 can be enabled.
• The ready-for-operation relay is open.
Quick stop active • The application can be reparameterized.
• The quick stop function is being executed.
• The drive function
1
 is enabled.
• The ready-for-operation relay is closed.
a) A disabled drive function means the same as a power part which is switched off and a reset application (e.g., reset ramp 
generator). This means that the drive is not following the reference value.
XDS 5000
V5.X
 ±0Rpm  0.0A
0: Self test
 ±0Rpm 0.0A
1: ONdisable
 ±0Rpm  0.0A
2: ReadyforON
 ±0Rpm  0.0A
3: Switched on
 ±0Rpm  0.0A
4: Enabled
Fault
No.X: type of fault
Fault
No.X: type of fault
 ±0Rpm  0.0A
7: Quick stop