Technical data

Commissioning an inverter
Operating Manual
ID 442281.00
WE KEEP THINGS MOVING
17
3
The following eight states exist in the standard device state machine in accor-
dance with the DRIVECOM profile for drive technology.
Display Designation Behavior
Or
Not ready to
switch on
The electronics are powered.
Self-test is running.
Initialization is running.
Drive function
a)
is disabled.
Ready-for-operation relay is open.
Switchon disable Software/hardware initialization is finished.
The application was reparameterizedn.
The drive function
1
is disabled.
The ready-for operation relay is closed.
The ASP 5001 option (safe torque off) is active.
Ready to switch
on
The application can be reparameterized.
The drive function
1
is disabled.
The ready-for-operation relay is closed.
Switched on The application can be reparameterized.
The drive function
1
is disabled.
The ready-for-operation relay is closed.
Operation
enabled
The application can be partially parameterized.
The drive function
1
is enabled.
The ready-for-operation relay is closed.
Fault The application can be partially parameterized.
The drive function
1
is disabled.
The ready-for-operation relay is closed.
Fault reaction
active
The application can be reparameterized.
An error-dependent action is being executed (dis-
able drive function or quick stop).
The drive function
1
can be enabled.
The ready-for-operation relay is open.
Quick stop active The application can be reparameterized.
The quick stop function is being executed.
The drive function
1
is enabled.
The ready-for-operation relay is closed.
a) A disabled drive function means the same as a power part which is switched off and a reset application (e.g., reset ramp
generator). This means that the drive is not following the reference value.
XDS 5000
V5.X
±0Rpm 0.0A
0: Self test
±0Rpm 0.0A
1: ONdisable
±0Rpm 0.0A
2: ReadyforON
±0Rpm 0.0A
3: Switched on
±0Rpm 0.0A
4: Enabled
Fault
No.X: type of fault
Fault
No.X: type of fault
±0Rpm 0.0A
7: Quick stop