Technical data
Diagnosis
Operating Manual
107ID 442281.00
WE KEEP THINGS MOVING
13
13.3.44 *ConfigStartERROR unknown scale
13.3.45 *ConfigStartERROR unknown limit
Resolution Level Response
The versions of configuration and firmware
do not match.
— The configuration does not start.
Possible cause Test Measure Acknowledgement
The configuration saved in the
Paramodule originates from a
newer inverter firmware that
recognises more scaling func-
tions.
— Apply a suitable configuration or firm-
ware via POSITool.
—
Resolution Level Response
The versions of configuration and firmware
do not match.
— The configuration does not start.
Possible cause Test Measure Acknowledgement
The configuration saved in the
Paramodule originates from a
newer inverter firmware that
recognises more limit value
functions.
— Apply a suitable configuration or firm-
ware via POSITool.
—