Technical data

Diagnosis
Operating Manual
105ID 442281.00
WE KEEP THINGS MOVING
13
13.3.40 *ConfigStartERROR parameters lost
13.3.41 *ConfigStartERROR remanents lost
Resolution Level Response
No parameter values are saved in the Par-
amodule.
The configuration does not start.
Possible cause Test Measure Acknowledgement
The control part was
switched off while A00
was active.
Apply a suitable configuration via
POSITool and then save it (A00)
Replace the Paramodule.
Resolution Level Response
No flag values are saved. The configuration does not start.
Possible cause Test Measure Acknowledgement
The A00 Save values
action was not per-
formed.
Apply a suitable configuration via
POSITool and then save it (A00)
Replace the Paramodule.