ACTpro IOM INPUT/OUTPUT MODULE Installation and Configuration Instructions for the ACTpro IOM Input/Output Module
CONTENTS Technical Specification................................................................................................1 Product Overview ........................................................................................................1 Features.........................................................................................................................1 ACTWinPro Support...................................................................................................
Technical Specification Voltage Current Consumption Communications Operating Temperature Mounting Installation Weight Dimensions Construction 12V DC 250mA RS485 to ACT2000/ACT3000 -10ºC to +50ºC Surface Indoors 375g 190mm/137mm/58mm Polycarbonate housing Product Overview This product is an 8 Input/8 Output device that allows the ACT3000 and ACT2000 to be used in applications where signalling to other equipment is required.
ACTPro IOM ver 1.0 Applications Elevator control In this application, a user presents a card to the proximity reader when he enters the cab. This enables the buttons for the floors the user has access to. The buttons stay on for a programmable amount of time (normally 5 seconds) and then switch off. Alarm Systems The unit can be programmed to fire a relay on alarm events such as tamper, door forced, mains fail etc.
ACTPro IOM ver 1.0 Installation Please see the diagram on the last page for complete wiring. The IOM Input/Output module is wired to the controller on the same RS-485 network as the DS100 Door stations. The IOMs are addressed using the DIP switches on the PCB. The IOMs are maybe given any address in the range 1 to 4. No configuration of the IOM is possible from the keypad, useful configuration can only be performed from ACTWinPro.
ACTPro IOM ver 1.0 Configuration All IOM Input/Output Module configurations are performed via ACTWinPro. Step 1. The IOM configuration is available from the Database drop-down menu. Click on the New icon database. to generate a new IOM input/output module in the Give the IOM a name and assign it a controller and the local I/O number. This number must be the same as the dipswitch setting on the IOM. Remember to tick the Enabled box. Finally, click the Accept icon . Step 2.
ACTPro IOM ver 1.0 For example, you may want the input to be monitored only during the day or only when a particular output is on. The Normally Open option allows the input to be in the normal state when the contact is open and active when the contact is closed. If the Supervised option is checked, then two 4k7 resistors are required (see the wiring diagram at the end of the manual). This allows the IOM to check for tampers and shorts across the input contacts.
ACTPro IOM ver 1.0 Elevator Control Elevator control is one particular application of the IOM ACTWinPro allows programming of users, permitting them access to different floors in an elevator lift shaft at different times. The outputs on the IOM are wired into an elevator controller. Up to 32 floors maybe controlled from a single ACT3000/2000. However controllers maybe networked giving control of more floors. Step 1. The first step is to select the Elevator Floor option for the output.
ACTPro IOM ver 1.0 Step 4. The next step is to create an Elevator Group. Follow the procedure as before by selecting Elevator Group from the Database drop-down menu and clicking the New icon. Assign the Floor Access Rights by selecting the floor group and the timezone when access is allowed. In the example below, Elevator Group 1 always allows access to the Smith & Co. Floor group. Step 5.
ACTPro IOM ver 1.0 A User Group must be created and the Elevator group assigned. This means that any user with this user group is allowed access to the floors assigned in the Elevator Group. Step 6. Finally a Door must be assigned to a Floor Group. This would be the Door that has the reader attached in the Elevator Cab. The Floor Group assigned would consist of all the possible floors that are available from the elevator. Go to the Doors Database and assign a Floor Group.
ACTPRO IOM IO Module Installation Installation of an IO Module requires the following (1) Wiring Inputs and Outputs. (2) Providing 12V Power. (3) Wiring IO Module A,B and 0V RS485 signals to the Controller. (4) Setting the IO Module address All Configuration of Input/Output Operation is performed from ACTwin Upto 4 IO Modules maybe connected a single ACT3000/2000 Controller. The IO Modules share the same network as Door stations (DS100s). Therefore a controller may support up to 16 Doors and 4 IO Modules.