Technical data
Maintenance, troubleshooting, spare parts and dismantling
36 – EN ACT 600 – 5000
SYMPTOM POSSIBLE CAUSE - SUGGESTED ACTION
Electronic
instrument
DMC24
The led
is
on or flashes.
With
led flashing: one or more service warnings are active.
With
led lighted: one or more service warnings are waiting to be reset. The
display shows the DewPoint temperature and the active or not reset service
warning.
The service warnings are displayed with the following messages :
1.
: PF1 – temperature probe failure T1 (DewPoint) – verify electric wiring
and/or replace probe.
2. : PF2 - temperature probe failure T2 (air IN) – verify electric wiring and/or
replace probe.
3.
: PF3 - temperature probe failure T3 (compressor suction) – verify electric
wiring and/or replace probe.
4.
: Hdp – DewPoint too high (higher than set HdA value) – see specific
paragraph.
5.
: Ldp - DewPoint too low - see specific paragraph.
6.
: drn – the condensate drainer does not work properly (DRN contact open- if
electronic drainer is installed) - see specific paragraph.
7.
: SrV - Service – maintenance notice time expired (parameter SrV) – carry
out planned maintenance and reset hour counter.
8.
: dt – compressor supply temperature too high (probe T4) – see specific
paragraph.
9.
: HCP – condensing pressure too high – see specific paragraph.
NOTE: after solving the problem, the services must be reset (press the keys
log
reset
simultaneously for at least 3 seconds).