Technical data
Maintenance, troubleshooting, spare parts and dismantling
ACT 600 – 5000 35 – EN
SYMPTOM POSSIBLE CAUSE - SUGGESTED ACTION
Electronic
instrument
DMC24
The led
is
on or flashes.
With
led flashing : one or more alarms are active and the display shows
and the active alarms.
With
led lighted : one or more alarms are waiting to be reset and the display
shows
and the alarms that are no longer active but not yet reset.
The alarms are displayed with the following messages :
1.
: HP - HPS pressure switch tripped (refrigerant high pressure) for condensing
pressure too high - see specific paragraph (NOTE : when problem is solved press
reset key on HPS pressure switch).
2.
: LP - LPS pressure switch tripped (low pressure) due to refrigerant pressure
too low - see specific paragraph.
3. : Con – during first startup – power phases of compressor are not
connected properly (see RPP on the electric diagram) – Change rotating direction
swapping two phases of the power supply of dryer. These changes have to be
done only by a qualified electrician. DO NOT BY PASS RPP PROTECTION: BY
OPERATING THE MACHINE IN WRONG ROTATING DIRECTION, THE
COMPRESSOR WILL FAIL IMMEDIATELY AND THE WARRANTY WILL BE
VOIDED.
4.
: Con – one phase of power supply of dryer is missing (see RPP on the
electric diagram) – restore the missing phase.
5. : Con – Reverse Phase Protector (RPP) is faulty – replace it.
6.
: Con – electric protection of compressor tripped (see Q1/QC1 on the electric
diagram)– reset and verify the dryer’s proper operation.
7.
: Con - if installed - thermal protection inside the compressor tripped (see
MC1 on wiring diagram – wait 30 minutes and try again.
8. : FAn - electric protection of fan tripped (see QV1 on the electric diagram) -
reset and verify the dryer’s proper operation (Air-Cooled).
9.
: FAn – thermal protection inside the fan/s tripped (see MF on wiring diagram
– wait 30 minutes and try again (Air-Cooled).
10.
: Hdt – compressor discharge temperature protection tripped due to very
high temperature (probe T4) – see specific paragraph.
11. : ICE – temperature inside exchanger (probe T1) too low – DewPoint is
too low - see specific paragraph.
12.
: LCP - condensing pressure too low – see specific paragraph.
13.
: PF4 – failure temperature probe T4 (compressor discharge) – verify
electric wiring and/or replace probe.
14.
: PFP – failure pressure transducer BHP (condensing pressure) – verify
electric wiring and/or replace transducer.
NOTE: after solving the problem, the alarms must be reset (press the keys
log
reset
simultaneously for 3 seconds).










